This allows the module to function with normally open or normally closed switches.
Four fully configurable auxiliary inputs are provided to give protection expansion.These can be selected to be indication, warning or shutdown inputs either immediate or held off during start up.
ALARM CHANNELS
Multiple alarm channels are provided to monitor the following:
Under/Overspeed
Charge Fail
Emergency Stop
Low oil pressure
High engine temperature
Fail to Start
Fail to stop
Loss of speed sensing
Programmable inputs as selected
First up alarm is indicated by a flashing LED. Subsequent simultaneous alarms are displayed by a steady LED.
DC SUPPLY
CONTINUOUS VOLTAGE RATING 8 to 35 V Continuous.
CRANKING DROPOUTS Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5V. This is achieved without the need for internal batteries.
MAXIMUM OPERATING CURRENT 290 mA at 12 V. 210 mA at 24 V.
MAXIMUM STANDY CURRENT 50 mA at 12 V. 30 mA at 24 V.
CHARGE FAIL EXCITATION RANGE 0 V to 35 V
INPUTS
ALTERNATOR INPUT RANGE 15 - 300 V ac RMS
ALTERNATOR INPUT FREQUENCY 50 - 60 Hz at rated engine speed. Magnetic Input Range: 0.5 V to +/- 70 V (Clamped by transient suppressors)
MAGNETIC INPUT FREQUENCY 10Hz to 10,000 Hz
OUTPUTS
START RELAY OUTPUT 16 Amp DC at supply voltage.
FUEL RELAY OUTPUT 16 Amp DC at supply voltage.
AUXILLIARY RELAY OUTPUTS 5 Amp DC at supply voltage.