Sensing Input/Power input 120(95132VAC)240(190-264),1 phase,2wire Magnetic field output Voltage:Max 90VDC at 207VAC input Current:Continuous 4A,intermittent 10A PRESSURE REGULATING ACCURACY <+/-%RMS with 4% engine governing
Sensing and Power Input: Voltage : 100- 264 V ac 1 phase Frequency: 50- 60 Hz nominal Output: Voltage: 82 V dc @ 200 V ac power input Voltage: 45 V dc @ 110 V ac power input Regulation: +-1%
Features: Voltage regulation < +/-1% Soft start voltage ramping Sensing voltage loss protection 120 or 240 Vac sensing, jumper selectable Under frequency roll off protection With under frequency LED indicator